Key points for installation of fire-fighting equipment
Author:
Source:
Delivery time:
23-05-17 15:40
1. A bus short-circuit isolator is installed on the system bus, with 32 points per isolator and set according to the fire compartment. (Different from the original design in terms of system and layout)
2. For buildings exceeding 100m, except for the controllers installed in the fire control room, each controlled fire detector, manual alarm, and module should not cross the refuge level.
3. Buildings with fire linkage functions should be equipped with fire control rooms.
4. The fire control room should have corresponding as-built drawings, descriptions of the control logic relationships of each subsystem, user manuals, system operating procedures, emergency plans, duty systems, maintenance systems, and cardboard records. (The design description should specify that the fire equipment company, fire construction unit, construction unit, and property management should jointly complete this project.)
5. It is strictly prohibited to pass through electrical circuits and pipelines unrelated to fire protection facilities in the fire control room.
Fire Equipment Company
6. Equipment layout and room size in the fire control room: single row layout with a small width of 5m, double row layout with a small width of 6m. The length of the room (calculated based on the width of the equipment 1000mm) is determined by the number of equipment. When the length of the equipment arrangement exceeds 4m, the channels at both ends should be greater than 1m.
7. Allow the fire control room to be shared with the weak current system, but there should be clear intervals. (Emphasized in the design description)
8. The control equipment for fire pumps (spray, rain, water curtains, fire hydrants), smoke prevention and exhaust fans should not only adopt linkage control methods, but also be equipped with manual direct control devices in the fire control room. (Fire protection direct starting line)
9. The automatic fire alarm system should be equipped with fire sound and light alarms, and all fire sound and light alarms inside the building should be activated after confirming the fire.
10. When the fire sound alarm is equipped with a voice prompt function, a voice synchronizer should also be set. (Emphasized in the design description)
11. When multiple fire sound alarms are installed in a unified building, the automatic fire alarm system should be able to simultaneously start and stop all fire sound alarms. (Emphasized in the design description)
12. The centralized alarm system and control center alarm system should be equipped with fire emergency broadcasting. (Actually, it's done by those who have a fire control room)
13. When used in conjunction with regular broadcasting or background music broadcasting, fire emergency broadcasting should have a mandatory entry function. (Emphasized in the design description)